Fire detector thermal SPT Tiras Ex point intrinsically safe 2-wire, designed to detect fires in their early stage in closed premises of buildings and structures, power supply 8-28 V, HP.
The detector reacts to exceeding the threshold value of the ambient temperature in the protected environment.
Mounted on the ceiling. The LED indicator flashes every second. Works with 2-wire loops.
The sensor is used to detect fire in a house, shop, hotel, restaurant, office building, school, bank, library, warehouse, etc.
Features:
• Designed for flash detection by the method of detection of exceeding the threshold value of the ambient temperature.
• The sensor is installed on the ceiling and is easy to set up, it is enough to know how to insert the wires into the terminals and read the instructions
• Equipped with a thermal sensor.
• Made in an organic design from high-quality and durable ABS plastic
• Conveniently attached to the ceiling using a special attachment
• LED indication every second shows the performance of the sensor
• Certified by the State Certification Center of the Ministry of Emergency Situations of Ukraine
• Supported by any central units of fire alarms that work with HP loops
• Powered by the central unit, 8-28 V DC
Characteristics:
• Sensor type: wired;
• Supply voltage: 8 - 28 V;
• Current consumption in standby mode: 0.15 mA;
• Current consumption during activation: no more than: 22 mA;
• Internal resistance of the detector at a current of 20 ± 2 mA: 510 Ohm;
• Operating temperature range during operation: -10 ° C to + 55 ° C;
• Maximum permissible relative humidity at +40°C: 93%;
• Degree of housing protection: IP 30;
• Diameter: 99 mm;
• Height: 54 mm;
• Weight: 0.15 kg.