Accumulator battery RITAR DC12-150, Gray Case, 12V 150Ah (495 * 185 * 280), Q1 AGM 12V 150 Ah.
DC series (deep cycle) rechargeable batteries are designed for frequent cyclic charges and discharges.
The DC series batteries have 30% more cyclic loads than the backup series.
Accumulator batteries of the DC series are intended for solar and wind energy, medical equipment, telecommunication equipment.
and UPS systems and others. The number of complete cycles is 300.
Features:
• Number of elements: 6
• Voltage: 12 V
• Nominal capacity: 150 A/h. with a 20-hour discharge up to 1.75 V per cell at 25 °C
• Weight: 44.5 kg (Tolerance ± 2.0%)
• Internal resistance: 4.2 mΩ
• Terminal type: F12 (M8)
• Maximum discharge current 1500 A (5 seconds)
• Short circuit current: - A
• Shelf life: 12 years
• Maximum charging current: 45 A
• Control capacity:
- C3 111.6 AH
- C5 125.5 AH
- C10 143.0 AH
- C20 150.0 AH
• Charge voltage in buffer mode: 13.6 V ~ 13.8 V at 25 ° C
• Temperature compensation: -3 mV/°C/cell
• Charge voltage in cyclic mode: 14.6 V ~ 14.8 V at 25 ° C
• Temperature compensation: -4 mV/°C/cell
• Operating temperature range:
- discharge: -20°C ~ 60°C
- charge: 0 ° C ~ 50 ° C
- storage: -20 ° C ~ 60 ° C
• Normal operating temperature range: 25±5°C
• Case material: A.V.S. UL94-HB, UL94-V0
• Self-discharge: RITAR Regulated Lead Acid (VRLA) rechargeable batteries can be stored for up to 6 months at 25°C, after which recharging is recommended. The monthly self-discharge rate is less than 3% at 25 °C. Please charge the batteries before use.