Power cable (N)HXH-J FE180/E30 5x4 fire-resistant (fire-resistant) halogen-free for fire alarm and automation, copper monocores, ability to maintain the integrity of electrical circuits E30, FE180, DIN VDE 0266 standard.
Characteristics: • Number of cores 5 cores • Cross-section thickness 4 mm² • Conductor material: copper • Outer diameter 13.86 mm • Cable mass 377.81 kg/km • Maximum core temperature during short circuit: +250°C • Temperature range: from –40°C to +70°C
Features: • preservation of insulation function under fire conditions: DIN VDE 0472-814 at least 3 hours, 800°C (FE 180), IEC 60331. • preservation of cable function under fire conditions with a fastening and supporting system: DIN 4102-12 for 30 minutes (E30). • Rated voltage: 0.6/1 kV. • Test voltage, alternating current: 50 Hz, 4000 V.
Application: • Halogen-free, high-security, fire-resistant cable is used in buildings with a large number of people and valuables. It is used for stationary laying on, under plaster, in dry, damp and wet rooms, in masonry, walls and in concrete, with the exception of direct laying in concrete during shaking and compaction. The cable can be used outdoors. Laying the cable in the ground is allowed, but when laid in protective hoses and pipes.
Construction: • Conductor: copper, solid or stranded, according to DIN VDE 0295 class 1 or class 2 • Insulation: special fire-resistant composition - structured fire-retardant polymer that ceramizes when exposed to fire, in accordance with VDE 0207 standard, section 22. • Sheath: structured polymer flame-retardant compound in orange color according to VDE 0207 standard.
Compliance with standards: • Fire resistance: DIN VDE 0472-804C, 0482-266-2-4, IEC 60332-3 • Smoke emission: DIN VDE 0472-816, 0482-267-2-4, IEC 61034 • Release of toxic and corrosive gases during combustion: - IEC 60754-1: acid gases < 0.5% - DIN VDE 0472-813, IEC 60754-2: pH≥4.3; • Specific conductivity: ≤100µScm-1 • Preservation of function in fire conditions: - cable with fastening and support system: DIN VDE 4102-12 - 30 minutes - insulation IEC 60331, DIN VDE 0472-814 fire resistance for - 180 minutes