Power cable; fire-resistant, halogen-free, does not spread / does not support burning, with preservation of the functions of the cable under fire conditions for 30 minutes; unshielded; 2 wires with a cross section of 1.5 mm2; for electrical networks with nominal voltage up to 0.66/1 kV; conductor material is copper; the outer shell is a halogen-free compound.
Application
It is used for permanent laying above and below plaster in dry, damp and wet rooms, as well as in stone masonry, walls and concrete. It is allowed to lay the cable in the ground, but under the condition that it is laid in protective hoses and pipes. Suitable for electrical networks with nominal voltage up to 0.66/1 kV.
Features
• Complies with standards: fire resistance DIN VDE 0472-804C, 0482-266-2-4, IEC 60332-3; smoke emission DIN VDE 0472-816, 0482-267-2-4, IEC 61034; release of toxic and corrosive gases during combustion: IEC 60754-1, acid gases < 0.5% DIN VDE 0472-813, IEC 60754-2: pH≥4.3, specific conductivity: ≤100µScm-1.
• Retention of function in fire conditions: cable with fastening system DIN VDE 4102-12 – 30 minutes, insulation IEC 60331, DIN VDE 0472-814, fire resistance for 180 minutes. The maximum core temperature during a short circuit: +250°C.
• Nominal voltage: 0.66/1 kV.
• The bending radius is at least seven times the minimum outer size of the cable.
• Material:
- insulation: silicone (silicone) rubber;
- shell: polymer halogen-free compound;
- core: copper conductor.
• Temperature range during installation and laying: from -10 to +50°С; operating temperatures with a fixed connection from -30 to +50 °C.
• The service life of the cable is at least 12 years.
Characteristics:
• Device type Fire-resistant cable
• Cable resistance 12.1 Ohm
• 12-month warranty.
• Cable type Power
• LSZH shell (halogen-free compound)
• The number of cores is 2
• Core material Copper (Cu)
• Core cross-section 1.5 mm²
• Color Orange